NYM










Application: In dry, damp and wet locations on premises and in store rooms with fire and explosion hazard.
Can be used outdoors but cannot be buried underground.
Techinical data: 1.5mm2 – 10mm2 are single-core, 10 and 16mm2 are multi-core. Insulation is TI 1 thermoplastic.
Twisted. Outer sheath color is grey.
Max. conductor temperature: 70°C
Rated voltage: 300/500V
















Rated Number of Conductor Insulation Outer Sheath Outer Weight Resistance
Crosssection Strands Diameter Thickness Thickness Diameter approx. at 20 °C
(mm²)
(mm) (mm) (mm) (mm) (kg/km) (mΩ/m)
2x1.5 1 1.38 0.6 1.4 8 116 12.1
2x2.5 1 1.80 0.7 1.4 10 160 7.28
2x4 1 2.26 0.8 1.4 11.4 218 4.56
2x6 1 2.80 0.7 1.4 12.4 277 3.03
2x10 1-7 4.10 1.0 1.6 16.4 488 1.83
2x16 1-7 5.20 1.0 1.6 18.6 600 1.15
3x1.5 1 1.38 0.6 1.4 9.2 136 12.1
3x2.5 1 1.80 0.7 1.4 10.5 189 7.28
3x4 1 2.26 0.8 1.4 12 262 4.56
3x6 1 2.80 0.8 1.6 13.5 353 3.03
3x10 1-7 4.10 1.0 1.6 17.4 601 1.83
3x16 1-7 5.20 1.0 1.6 20 856 1.15
4x1.5 1 1.38 0.6 1.4 10 163 12.1
4x2.5 1 1.80 0.7 1.4 11.3 231 7.28
4x4 1 2.26 0.8 1.6 13.4 236 4.56
4x6 1 2.80 0.8 1.6 15 452 3.03
4x10 1-7 4.10 1.1 1.6 19 746 1.83
4x16 1-7 5.20 1.0 1.6 22 1071 1.15